RZ1-K (AS) 0,6/1kV

 

rz1-k_b_webconsombra.jpg

 

Description


 

These halogen-free cables are suitable for transport and permanent installations, protected or unprotected, where low fumes and corrosive gas emission is required in the event of fire, such as public premises, hospitals, school, shopping centres and airports. They are suitable for indoor and outdoor installations.


Their flexibility makes them very appropriate in complex and extremely difficult installations.

Applications


 


  • Underground supply networks for outdoor lighting installations

They can also be used in the following applications:


  • Underground networks for low voltage distribution
  • Electricity distribution networks. Underground service connections
  • Installations in premises with special characteristics


Appropriate for installations where greater fire protection is required.
industrial.gif

90.gif

flexible.gif

as.gif

th_rosh
productologo.jpg

 

 

Technical Characteristics

RZ1-K (AS) 0,6/1kV

 

rz1-k.jpg detallerz1.jpg

 

 

 

 

1. Conductor

Flexible electrolytic copper conductor (Class V) according to BS EN 60228:2005.

2. Insulation

Cross-linked polyethylene insulation(XLPE), type DIX-3, according to HD 603S1

3. Sheathing

Thermoplastic polyolefin sheath according to UNE 21123.

Rated voltage

0,6/1kV

Test voltage

3.500V in A.C.

Maximum temperature

90ºC

Other characteristics

  • Colours UNE 21089 and HD 303S2:2001
  • Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
  • Non-fire propagating according to UNE-EN 50266 and EN 50266
  • Low halogen content according to UNE-EN 50267 and EN 50267
  • Low corrosive gas emission according to UNE-EN 50267 and EN 50267
  • Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
  • The use of cross-linked polyethylene (XLPE) admits greater current density, at equal section, respect to the insulation with PVC.

National norm / european

EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034
International norm
IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034

 

Dimensions

RZ1-K (AS) 0,6/1kV

 

Section (mm2)

Resistance at 20ºC (Ω/Km)

External Diameter (mm)

Weight (kg/km)




Section (mm2)

Resistance at 20ºC
(Ω/Km)

External
Diameter
(mm)

Weight
(kg/km)

1x1,5

13,30

5,70

50




3x4

4,95

11,07

210

1x2,5

7,98

6,12

60




3x6

3,30

12,25

275

1x4

4,95

6,65

75




3x10

1,91

14,31

420

1x6

3,30

7,20

95




3x16

1,21

16,47

605

1x10

1,91

8,15

140




3x25

0,780

20,03

915

1x16

1,21

9,15

195




3x35

0,554

22,66

1.240

1x25

0,780

10,80

290




4x1,5

13,30

9,92

140

1x35

0,554

11,90

380




4x2,5

7,98

10,93

190

1x50

0,386

13,50

520




4x4

4,95

12,22

255

1x70

0,272

15,60

720




4x6

3,30

13,55

345

1x95

0,206

17,35

930




4x10

1,91

15,85

535

1x120

0,161

19,40

1.175




4x16

1,21

18,27

775

1x150

0,129

21,40

1.455




4x25

0,780

22,36

1.175

1x185

0,106

23,30

1.745




4x35

0,554

25,07

1.580

1x240

0,0801

26,60

2.315




4x50

0,386

29,21

2.205

1x300

0,0641

30,20

2.895




4x70

0,272

32,00

2.905

1x400

0,0486

34,80

3.935




4x95

0,206

35,60

3.755

2x1,5

13,30

8,55

100




5x1,5

13,30

10,79

170

2x2,5

7,98

9,39

130




5x2,5

7,98

11,93

230

2x4

4,95

10,45

175




5x4

4,95

13,37

315

2x6

3,30

11,55

225




5x6

3,30

14,87

425

2x10

1,91

13,45

335




5x10

1,91

17,45

655

2x16

1,21

15,45

475




5x16

1,21

20,17

945

2x25

0,780

18,75

710




5x25

0,780

24,80

1.450

3x1,5

13,30

9,01

115




5x35

0,554

27,40

1.960

3x2,5

7,98

9,92

135




5x50

0,386

33,50

2.885

 

Cables available with up to 61 conductors

Cables with more than 3 conductors can be manufactured with one of the primaries yellow/green.

Documents

RZ1-K (AS) 0,6/1kV

 

 

 

pdflogo2.jpg