These cables are suitable for the transport and distribution of electricity in permanent installations, having been designed to be able to guarantee service subject to fire conditions. They are mainly applicable in non-autonomous safety circuits and in circuits in operation with centralised autonomous sources, which must remain in service during and after the fire. Furthermore, subject to fire, they must not emit acid or toxic gases so they guarantee the safety of people and of the installations, at the same time as they facilitate the evacuation and intervention of the emergency teams on emitting reduced opacity gases.
Applications
Public premises
Appropriate for installations where greater fire protection is required and to guarantee the operation of installations subject directly to fire, for 90 minutes at 400ºC.
Technical Characteristics
RZ1-K MICA (AS+) 0,6/1kV
1. Conductor
lexible electrolytic copper conductor(Class V) according to BS EN 60228:2005 (previously BS6360)and UNE 60228.
2.Insulation
3. Insulation
Mica tape
Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1.
4. Sheathing
Thermoplastic polyolefin sheath according to UNE 21123.
Rated voltage
0,6/1kV
Test voltage
3.500V en C.A.
Maximum temperature
90ºC
Other characteristics
Colours according to UNE 21089 and HD 303S2:2001
Fire resistance according to UNE-EN 50200, EN 50200, UNE-EN 50362, EN 50362 and IEC60331
Non-flame propagating according to UNE-EN 60332, EN 60332, IEC 60332
Non-fire propagating according to UNE-EN 50266, EN 50266
Low halogen content according to UNE-EN 50267, EN 50267
Low corrosive gas emission according to UNE-EN 50267, EN 50267
Low opaque smoke emission according to UNE-EN 61034, EN 61034, IEC 61034
National norm / european
EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034