Description
These cables are suitable for use in housing. To supply household appliances even in the case of heating and kitchens if there is no risk of contact with hot parts.
These cables are suitable for use in domestic installations, housing and similar premises. Mainly to supply household appliances even in the case of heating and kitchens if there is no risk of contact with hot parts.
1. Conductor
Electrolytic copper conductor, Class I and II, according to BS EN 60228:2005 (previously BS6360) and UNE 60228.
2. Insulation
Insulation TM-1 according to 21031-4, HD 21.4S2:1990, IEC 227-4:1979 MOD and NF C32-207/A1
3. Sheathing
Sheath TM-1 according to 21031-4 , HD 21.4S2:1990, IEC 227-4:1979 MOD and NF C32-207/A1
Rated voltage
300/500V
Test voltage
2.000V in A.C.
Maximum temperature
70ºC
Other characteristics
Colours according to UNE 21089 and HD 303S2:2001
Non-flame propagating according to UNE-EN 60332-1, EN 60332, IEC 60332 and NF C32-070
PVC insulation with reduced hydrogen chloride (HCL) emission
National norm / european
EN 60332-1
International norm
IEC 60332-1
Section (mm2 )
Resistance at 20ºC (Ω/Km)
External Diameter (mm)
Weight (kg/Km)
2x1,5
12,10
10,50
130
2x2,5
7,41
12,00
170
2x4
4,61
13,00
221
2x6
3,08
14,00
278
2x10
1,83
15,70
465
2x16
1,15
20,00
641
2x25
0,727
24,00
921
3x1,5
12,10
11,00
137
3x2,5
7,41
12,50
214
3x4
4,61
13,50
277
3x6
3,08
15,50
362
3x10
1,83
19,00
571
3x16
1,15
21,50
790
3x25
0,727
26,00
1.156
4x1,5
12,10
12,00
169
4x2,5
7,41
13,50
261
4x4
4,61
15,00
351
4x6
3,08
17,00
437
4x10
1,83
20,50
680
4x16
1,15
23,50
1.007
4x25
0,727
28,50
1.487
5x1,5
12,10
12,50
211
5x2,5
7,41
14,50
314
5x4
4,61
17,00
417
5x6
3,08
18,50
553
5x10
1,83
22,00
842
5x16
1,15
26,00
1.266
5x25
0,727
31,50
1.827
Cables with more than 3 conductors can be manufactured with one of the primaries yellow/green.