Description
|
Description
These cables are halogen-free flexible and are suitable for fixed installations in places of public competition and where in case of fire is required low emission of smoke and corrosive gases such as hospitals, schools, malls, airports, and in all facilities in which you want increase protection against fire. The use of this product range easy to install, reducing time and cost of implementation.Available in various color combinations.
This product is manufactured according to the utility model (patent) owned 200,702,014 No. RCT Cables
Applications
- Individual Derivation
- Indoor and reception facilities
- Public premises
- Local installations of fire or explosion risk
Suitable for installations that require increased protection from fire, even in homes.
|
Technical Characteristics
|
1. Conductor
|
Flexible electrolytic copper (class V) according to BS EN 60228:2005 (previously BS6360) and EN 60228. |
|
2. Isoliermaterial
|
Halogen-free thermoplastic material such as UNE TI-7 and 211,002 HD 21.15S1: 2006 |
|
Rated voltage
|
450/750V |
|
Test voltage
|
2.500V in A.C. |
|
Maximum temperature
|
70ºC |
|
Other characteristics
|
- Colors from 21,031 UNE and HD 21.1S4: 2002
- No flame spread according to UNE-EN 60,332, IN 60,332, IEC 60332
- Fire-retardant according to UNE-EN 50266, EN 50266
- Halogen low as 211,002 UNE Annex A, HD 21.15S1: 2006
- Low corrosive gas emission according to UNE 211,002 Annex A, HD 21.15S1: 2006
- Low opaque smoke emission opaque according to UNE-EN 61034, EN 61034, IEC 6103
|
|
National norm / european
|
EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034 |
|
International norm
|
IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034 |
Dimensions
| Section (mm2) |
Resistance at 20ºC (Ω/Km) |
External Diameter (mm) |
Weight (kg/km) |
| 3x1,5 |
13,30 |
6,26 |
56 |
| 3x2,5 |
7,98 |
7,78 |
90 |
Cables with more than 3 conductors can be manufactured with one of the primaries yellow/green. Available in different colour combinations.