18/05/12 Cu: 7795$ 6128€
SOZ1-K (AS+) 300/500V PDF Print E-mail

Description

SOZ1-K (AS+) 300/500V

SOZ1-Ksombra.jpg

Description


These halogen-free cables are indicated for use in electric circuits for fire detection, alarms, pushbuttons, detectors, etc. Furthermore, this cable guarantees compliance with the applicable legislation, satisfying the fire resistance standard UNE-EN 50200, thus maintaining the operation of the installations when subject to fire, for 90 minutes at 400ºC, as established by the REBT in its ITC 28 “public premises”. Subject to fire it does not emit acid or toxic gases so it guarantees the safety of people and of the installations.

Applications


  • Public premises

According to the Regulation on Safety against Fire in Industrial Establishments, 2004 According to basic document SI, safety in case of fire, of the Technical Building Code, March 2006. Appropriate for installations where greater fire protection is required and to guarantee the operation of installations directly subject to fire.

industrial.gif flexible.gif 90.gif

as+.gif

iman.gif

400.gif

 

Technical Characteristics

SOZ1-K (AS+) 300/500V

 

SOZ1-Kconstruccion.jpg
SOZ1-Kdetalle.jpg

 

1. Conductor

Flexible electrolytic copper (Class V) according to BS EN 60228:2005 (previously BS6360) and UNE 60228.

2. Insulation

Silicone insulation, type EI-2, according to UNE-EN 50363.

3. Screen

Polyester tape, tinplated copper drainage wire and polyester aluminium tape.

4. Sheathing

Halogen-free thermoplastic polyolefin sheath according to UNE 21123, non-fire propagating and with reduced smoke emission and opacity.
Rated voltage

300/500 V

Test voltage

2.000V in A.C.

Maximum Temperature

90ºC

Other characteristics
  • Primary colours, red and black
  • Fire resistance according to UNE-EN 50200, EN 50200, UNE-EN 50362 and EN 50362
  • Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
  • Non-fire propagating according to UNE-EN 50266 and EN 50266
  • Low halogen content according to UNE-EN 50267 and EN 50267
  • Low corrosive gas emission according to UNE-EN 50267 and EN 50267
  • Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034

National norm / european

EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034 / UNE-EN 50200 / UNE-EN 50363
International norm
IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034 / IEC 60331

Dimensions

SOZ1-K (AS+) 300/500V

 

Section
(mm2)

Resistance at 20ºC (Ω/Km)

External Diameter (mm)

Weight (kg/Km)

2x1,5

13,30

8,60

105

2x2,5

7,98

9,90

135

 


 

Documents

SOZ1-K (AS+) 300/500V

 

pdflogo2.jpg