These halogen-free cables are indicated for use in electric circuits for fire detection, alarms, pushbuttons, detectors, etc. Furthermore, this cable guarantees compliance with the applicable legislation, satisfying the fire resistance standard UNE-EN 50200, thus maintaining the operation of the installations when subject to fire, for 90 minutes at 400ºC, as established by the REBT in its ITC 28 “public premises”. Subject to fire it does not emit acid or toxic gases so it guarantees the safety of people and of the installations.
Applications
Public premises
According to the Regulation on Safety against Fire in Industrial Establishments, 2004 According to basic document SI, safety in case of fire, of the Technical Building Code, March 2006. Appropriate for installations where greater fire protection is required and to guarantee the operation of installations directly subject to fire.
Technical Characteristics
SOZ1-K (AS+) 300/500V
1. Conductor
Flexible electrolytic copper (Class V) according to BS EN 60228:2005 (previously BS6360)and UNE 60228.
2. Insulation
Silicone insulation, type EI-2, according to UNE-EN 50363.
3. Screen
Polyester tape, tinplated copper drainage wire and polyester aluminium tape.
4. Sheathing
Halogen-free thermoplastic polyolefin sheath according to UNE 21123, non-fire propagating and with reduced smoke emission and opacity.
Rated voltage
300/500 V
Test voltage
2.000V in A.C.
Maximum Temperature
90ºC
Other characteristics
Primary colours, red and black
Fire resistance according to UNE-EN 50200, EN 50200, UNE-EN 50362 and EN 50362
Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
Non-fire propagating according to UNE-EN 50266 and EN 50266
Low halogen content according to UNE-EN 50267 and EN 50267
Low corrosive gas emission according to UNE-EN 50267 and EN 50267
Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
National norm / european
EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034 / UNE-EN 50200 / UNE-EN 50363