These cables are indicated for executing permanent installations where fire resistance is required as well as electromagnetic protection to avoid parasitic currents. They are useful for control applications of drivers, solenoid valves, start-up of machines and robots, remote switches, temperature, intensity or voltage regulation in motorised valves as well as for installations in computer centres, airports, road tunnels, railways and anywhere where low fumes and corrosive gas emission is required in the case of fire, such as public premises, hospitals, schools and shopping centres.
Applications
Public premises
Appropriate for installations where greater fire protection is required and to guarantee the operation of installations directly subject to fire, for 90 minutes at 400ºC.
Technical Charcteristics
SZ1C4Z1-K (AS+) 0,6/1kV
1. Conductor
Flexible electrolytic copper (Class V) according to BS EN 60228:2005 (previously BS6360)and UNE 60228.
2. Insultaion
Silicone insulation, type EI-2, according to UNE-EN 50363.
3. Screen bedding
Thermoplastic Polyolefin.
4. Screen
70% copper braid on polyester sheet.
5. Sheathing
Thermoplastic polyolefin sheath according to UNE 21123
Rated voltage
0,6/1kV
Test voltage
3.500V in A.C.
Maximum temperature
90ºC
Other characteristics
Colours according to UNE 21089 and HD 303S2:2001
Fire resistance according to UNE-EN 50200, EN 50200, UNE-EN 50362 and EN 50362
Non-flame propagating according to UNE-EN 60332, EN 60332 and IEC 60332
Non-fire propagating according to UNE-EN 50266 and EN 50266
Low halogen content according to UNE-EN 50267 and EN 50267
Low corrosive gas emission according to UNE-EN 50267 and EN 50267
Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
National norm / european
EN 60332-1 / EN 50266 / EN 50267-1 / EN 50267-2 / EN 61034 / UNE-EN 50200 / UNE-EN 50363