(+34) 976 500 120 | Contact us

H07Z-K

H07Z-K

Description


The H07Z-K cables comply with the construction product classification criteria according to the EU CPR Regulation 305/2011 and EN 50575 , being those suitable for setting up wiring installations for panels, especially when a low fume and corrosive gas emission and improved behaviour with temperature is required.

Reference Standards

UNE-EN 50525-3-41, EN 50525-3-41, IEC 60227-3

Applications

Suitable for the following installations:
  • Meter centralization
  • Premises with public attendance

Industrial Maximum temperature 90 ºC Flexible Aenor Certificate HAR Certificate RoHS CPR rated

Technical Characteristics

H07Z-K H07Z-K
1. Conductor

Class V Electrolyte copper in accordance with UNE-EN 60228, EN 60228

2. Insulation

Thermosetting material with polyolefin base with low fume and corrosive gases emission, type EI-5 in accordance with UNE 21027-9 and HD 22.9S3:2007

Nominal voltage

450/750V

Test voltage

2.500 V A.C.

Maximum temperature

90 ºC

Other characteristics

Colours in accordance with UNE 21027 and HD 22.1S4
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
Low halogen content in accordance with UNE 21027-9, HD 22.9S3:2007 and IEC 60754-1 and 60754-2-2
Low corrosive gases emission in accordance with UNE 21027-9, HD 22.9S3:2007 and IEC 60754-1 and 60754-2-2
Low opaque fume emission in accordance with UNE-EN 61034, EN 61034 and IEC 61034
Curvature radius up to 16mm2: 4 x external diameter
Curvature radius from 25mm2 to 35mm2: 5 x external diameter
Curvature radius from 50mm2 on: 6 x external diameter
CPR Classification according to EN 50575

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)
Class

1x1,5

13,3

2,90

18

Dca- s2, d2, a2

1x2,5

7,98

3,50

29

Dca- s2, d2, a2

1x4

4,95

4,00

43

Dca- s2, d2, a2

1x6

3,3

4,50

59

Dca- s2, d2, a2

1x10

1,91

5,90

103

Dca- s2, d2, a2

1x16

1,21

6,85

153

Dca- s2, d2, a2

1x25

0,78

8,50

231

Dca- s2, d2, a2

1x35

0,554

9,80

316

Dca- s2, d2, a2

1x50

0,386

11,60

452

Dca- s2, d2, a2

1x70

0,272

13,45

639

Dca- s2, d2, a2

1x95

0,206

16,00

855

Dca- s2, d2, a2

1x120

0,161

17,80

1.102

Dca- s2, d2, a2

1x150

0,129

19,60

1.357

-

1x185

0,106

21,60

1.652

-

1x240

0,0801

24,15

2.092

-

Documents