(+34) 976 500 120 | Contact us

Description


RZ1FZ1-K mica cables are suitable for the transport and distribution of electrical power in fix installations, and they are designed to guarantee the service under fire conditions. They are mainly useful in non-autonomous security circuits and in circuits in service with centralised autonomous sources, which must be in service during and after the fire.
Furthermore, in case of fire, it will not emit neither acid nor toxic gases ensuring the security of persons as well as premises, while easing the evacuation and intervention of the emergency teams because emitting low opacity gases. The metallic band provides a higher protection against mechanical aggressions and rodents. Its flexibility lets them be very appropriate for complex and very difficult installations.


Reference Standards

UNE 211025

Applications

  • Public premises

Appropriate for installations where greater fire protection is required and to guarantee the operation of installations subject directly to fire, for 90 minutes at 400 ºC.


Industrial Maximum temperature 400 ºC High Safety + Flexible Fire resistant RoHS

Technical Characteristics

RZ1FZ1-K mica (AS+) 0,6/1 kV RZ1FZ1-K mica (AS+) 0,6/1 kV
1. Conductor

Flexible electrolytic copper (Class V) according to UNE-EN 60228, EN 60228 and IEC 60228

2-3. Insulation

Mica tape / cross-linked polyethylene (XLPE), type DIX-3 according to UNE 21123 and HD 603S1

4. Armour bedding

Thermoplastic polyolefin

5. Metallic armour

Steel band

6. Sheath

Halogen Free Thermoplastic polyolefin according to UNE 21123

Nominal voltage

0,6/1 kV

Maximum temperature

90 ºC

Other characteristics

Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors)
Fire resistance according to UNE-EN 50200, EN 50200, UNE-EN 50362 and EN 50362
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
Non-fire propagating in accordance with UNE-EN 60332-3-24, EN 60332-3-24 and IEC 60332-3-24
Low halogen content according to IEC 60754-1 and 60754-2
Low corrosive gas emission according to IEC 60754-1 and 60754-2
Low opaque smoke emission according to UNE-EN 61034, EN 61034, IEC 61034

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)

2x1,5

13,3

12,20

235

2x2,5

7,98

13,30

285

3G1,5

13,3

12,90

267

3G2,5

7,98

13,90

319

3G4

4,95

16,00

431

3G6

3,3

17,60

537

3G10

1,91

19,50

704

3x16

1,21

22,40

963

3x25

0,78

26,25

1.357

3x35

0,554

28,40

1.690

3x50

0,386

34,10

2.404

4x4

4,95

16,80

484

4x10

1,91

22,20

901

4x16

1,21

25,90

1.260

5x1,5

13,3

14,70

342

5x2,5

7,98

15,90

415

5x10

1,91

22,70

971

7x1,5

13,3

16,00

414

Documents

Newsletter

The data gathered through the next form will be used to send communications on our products and services. We use Elastic Email as our marketing automation service. By sending this form you agree with the transfer of the data to Elastic Email to be processed according to their terms of use and privacy policy.

Responsible: Cables RCT S.A.U. Purpose: To manage the submission of information and commercial prospecting. Legitimation: consent of the interested party. Recipients: Data will be transferred to Elastic Email for the automation of the submission. Rights: Access, correction and data erasure, as well as other rights, as explained in the additional information.Additional information on data protection is available on our website’s privacy policy