Description
These halogen-free cables are suitable for the execution of individual by-passes, in those cases where the supply is carried out with three or five conductors plus the tracer thread, red 1.5 section conductor, incorporating it onto the inside of the sheath. The aim of this product is to facilitate installation, reducing the time spent handling each conductor individually, as well as to avoid possible damage to the tracer thread due to its reduced section. Their flexibility makes them very appropriate in complex and extremely difficult installations.
Reference Standards
HD 603 S1 and IEC 60502
Technical Characteristics


1. Conductor |
Flexible electrolytic copper conductor (Class V) according to BS EN 60228:2005 (previously BS6360) and UNE 60228. |
---|---|
2. Insulation |
Cross-linked polyethylene insulation (XLPE), type DIX-3, according to UNE-HD 603-1 |
3. Sheath |
Thermoplastic polyolefin sheath according to UNE-HD 603-1 and ST8 according to IEC 60502-1 |
Maximum temperature |
90 ºC |
Nominal voltage |
0,6/1 kV |
Test voltage |
3.500 V A.C. |
Other characteristics |
Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors) |
Dimensions
Section (mm2) |
Resistance at 20 °C (Ohm/km) |
External Diameter (mm) |
Weight (kg/km) |
---|---|---|---|
3x6 + 1,5 |
3,3 |
11,25 |
267 |
3x10 + 1,5 |
1,91 |
13,10 |
399 |
3x16 + 1,5 |
1,21 |
15,40 |
580 |
3x25 + 1,5 |
0,78 |
18,90 |
899 |
3x35 + 1,5 |
0,554 |
21,95 |
1.182 |
3x50 +1,5 |
0,386 |
27,35 |
1.746 |
3x70 + 1,5 |
0,272 |
30,75 |
2.420 |
5x6 + 1,5 |
3,3 |
13,60 |
405 |
5x10 + 1,5 |
1,91 |
16,10 |
632 |
5x16 + 1,5 |
1,21 |
18,90 |
930 |
5x25 + 1,5 |
0,78 |
23,30 |
1.388 |
5x35 + 1,5 |
0,554 |
26,40 |
1.894 |