(+34) 976 500 120 | Contact us

Description


The XGB-F2 cables comply with the construction product classification criteria according to the EU CPR Regulation 305/2011 and EN 50575, being those recommended to transport and distribute low voltage electrical energy. Recommended for industrial connections, supplies, internal distribution and outdoor connections. They can be used in sub-surface networks and permanent installations.


Reference Standards

IEC 60502 and NBN HD 604-5L

Applications

Suitable for the following installations:
  • Sub-surface power source networks for outdoor lighting installations
  • General supply line
  • Individual bypass
  • Interior or receptor installations
  • Public premises
  • Sub-surface networks for low voltage distribution
  • Electric energy distribution networks. Sub-surface supply lines
  • Installations in premises with special features

Suitable for installations where there is a need to increase protection against fire hazards.

Industrial Maximum temperature 90 ºC High Safety RoHS CPR rated

Technical Characteristics

XGBF2 XGBF2
1. Conductor

Rigid electrolytic copper Class I to sections of 10 mm2 and class II for greater according to NBN-EN 60228, EN 60228 and IEC 60228.

2. Insulation

Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1

3. Sheath

Thermoplastic polyolefin sheath according to HD 603-1

Nominal voltage

0,6/1 kV

Test voltage

3.500 V A.C.

Maximum temperature

90 ºC

Other characteristics

Colours according to HD 308 S2
Non-flame propagation in compliance with NBN C30 004 F1, EN 60332-1-2 and IEC 60332-1-2
Non-fire propagation in compliance with EN 50399, NBN C30 004 F2, EN 60332-3-24 and IEC 60332-3-24
Low emission of halogen and corrosive gases in compliance with IEC 60754-1 and 60754-2
Low emission of opaque fumes in compliance with NBN C30 004 SD and IEC 61034-1
The use of cross-linked polyethylene (XLPE) allows a greater density of current, equality of cross-section, when compared to insulation with PVC
CPR Classification according to EN 50575

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)
Class

1x1,5

12,1

6,45

55

Cca- s1b. d1. a1

1x2,5

7,41

6,75

66

Cca- s1b. d1. a1

1x4

4,61

7,35

86

Cca- s1b. d1. a1

1x6

3,08

7,95

108

Cca- s1b. d1. a1

1x10

1,83

8,80

150

Cca- s1b. d1. a1

1x16

1,15

10,00

211

Cca- s1b. d1. a1

1x25

0,727

11,45

314

Cca- s1b. d1. a1

1x35

0,524

12,80

412

Cca- s1b. d1. a1

1x50

0,387

14,70

560

Cca- s1b. d1. a1

2x1,5

12,1

9,50

131

Cca- s1b. d1. a1

2x2,5

7,41

10,10

159

Cca- s1b. d1. a1

2x4

4,61

11,50

217

Cca- s1b. d1. a1

2x6

3,08

12,60

276

Cca- s1b. d1. a1

2x10

1,83

14,10

382

Cca- s1b. d1. a1

2x16

1,15

16,10

534

Cca- s1b. d1. a1

2x25

0,727

19,30

802

Cca- s1b. d1. a1

2x35

0,524

22,00

1.065

Cca- s1b. d1. a1

3G1,5

12,1

9,75

143

Cca- s1b. d1. a1

3G2,5

7,41

10,00

170

Cca- s1b. d1. a1

3G4

4,61

12,05

256

Cca- s1b. d1. a1

3G6

3,08

14,75

312

Cca- s1b. d1. a1

3G6

3,08

13,20

331

Cca- s1b. d1. a1

3x10

1,83

14,75

467

Cca- s1b. d1. a1

3x16

1,15

17,10

674

Cca- s1b. d1. a1

3x25

0,727

20,45

1.015

Cca- s1b. d1. a1

4x1,5

12,1

10,80

176

Cca- s1b. d1. a1

4x2,5

7,41

11,50

221

Cca- s1b. d1. a1

4x4

4,61

12,95

305

Cca- s1b. d1. a1

4x6

3,08

14,30

400

Cca- s1b. d1. a1

4G6

3,08

14,30

400

Cca- s1b. d1. a1

4x10

1,83

16,10

577

Cca- s1b. d1. a1

4x16

1,15

18,50

827

Cca- s1b. d1. a1

4x25

0,727

22,35

1.265

Cca- s1b. d1. a1

5G1,5

12,1

11,50

201

Cca- s1b. d1. a1

5G2,5

7,41

12,25

254

Cca- s1b. d1. a1

5G4

4,61

13,95

358

Cca- s1b. d1. a1

5x6

3,08

15,00

421

Cca- s1b. d1. a1

5G6

3,08

15,45

471

Cca- s1b. d1. a1

5x10

1,83

17,10

687

Cca- s1b. d1. a1

5G16

1,15

20,20

992

Cca- s1b. d1. a1

5x25

0,727

24,50

1.523

Cca- s1b. d1. a1

Newsletter

The data gathered through the next form will be used to send communications on our products and services. We use Elastic Email as our marketing automation service. By sending this form you agree with the transfer of the data to Elastic Email to be processed according to their terms of use and privacy policy.

Responsible: Cables RCT S.A.U. Purpose: To manage the submission of information and commercial prospecting. Legitimation: consent of the interested party. Recipients: Data will be transferred to Elastic Email for the automation of the submission. Rights: Access, correction and data erasure, as well as other rights, as explained in the additional information.Additional information on data protection is available on our website’s privacy policy