(+34) 976 500 120 | Contact us

Description


RZ1C4Z1-K mica (AS+) cables are suitable for permanent installations where fire resistance is required as well as electromagnetic protection to avoid parasitic currents. Useful in applications for the control and command of inverters, solenoid valves, machine and logic controller start-up, power switches, temperature, current or voltage regulation in motorised valves as well as for installation in computing facilities, airports, road tunnels, railway networks and wherever a low emission of corrosive fumes and gases is required due to fire hazards such as public premises, hospitals, schools and shopping centres.

Reference Standards

HD 603 S1 and IEC 60502

Applications

Suitable for:
  • Public premises

Suitable for facilities requiring an increased fire protection and a guaranteed functioning of facilities directly subjected to fire for a period of 90 minutes at 400 ºC.

Industrial Maximum temperature 90 ºC High Safety + Flexible Fire resistant Electromagnetic shielding RoHS

Technical Characteristics

RZ1C4Z1-K mica (AS+) 0,6/1 kV RZ1C4Z1-K mica (AS+) 0,6/1 kV
1. Conductor

Flexible electrolytic copper (Class V) in compliance with UNE-EN 60228, EN 60228 and IEC 60228

2. Insulation

Mica tape

3. Insulation

Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1

4. Armour bedding

Thermoplastic polyolefin

5. Metallic armour

70% copper braid on polyester sheet

6. Sheath

Halogen-free thermoplastic polyolefin sheath according to UNE 21123, non-fire propagating and with reduced smoke emission and opacity

Nominal voltage

0,6/1 kV

Test voltage

3.500 V A.C.

Maximum temperature

90 ºC

Other characteristics

Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors)
Fire resistant in compliance with UNE-EN 50200, EN 50200, UNE-EN 50362 and EN 50362
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
Non-fire propagating in accordance with UNE-EN 60332-3-24, EN 60332-3-24 and IEC 60332-3-24
Low halogen content in compliance with IEC 60754
Low emission of corrosive gases in compliance with IEC 60754-1 e IEC 60754-2
Low emission of opaque fumes in compliance with UNE-EN 61034, EN 61034 and IEC 61034

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)

1x95

0,206

21,85

1.168

1x120

0,161

23,60

1.432

1x150

0,129

26,30

1.777

1x185

0,106

28,20

2.077

1x240

0,0801

31,50

2.682

1x300

0,0641

33,60

3.193

2x25

0,78

24,90

1.074

2x35

0,554

27,00

1.330

2x50

0,386

32,35

1.898

2x70

0,272

36,05

2.455

2x95

0,206

39,50

3.065

3x25

0,78

26,40

1.306

3x35

0,554

28,50

1.629

3x50

0,386

34,30

2.339

3x70

0,272

38,20

3.051

3x95

0,206

41,75

3.831

4x25

0,78

27,10

1.472

4x35

0,554

30,85

1.977

4x50

0,386

38,90

3.003

4x70

0,272

42,20

3.807

4x95

0,206

46,75

4.864

5x16

1,21

26,60

1.314

5x25

0,78

30,95

1.851

5x35

0,554

34,30

2.408

5x50

0,386

41,70

3.496

5x70

0,272

46,25

4.561

5x95

0,206

50,50

5.749

Documents

Newsletter

The data gathered through the next form will be used to send communications on our products and services. We use Elastic Email as our marketing automation service. By sending this form you agree with the transfer of the data to Elastic Email to be processed according to their terms of use and privacy policy.

Responsible: Cables RCT S.A.U. Purpose: To manage the submission of information and commercial prospecting. Legitimation: consent of the interested party. Recipients: Data will be transferred to Elastic Email for the automation of the submission. Rights: Access, correction and data erasure, as well as other rights, as explained in the additional information.Additional information on data protection is available on our website’s privacy policy