Description
These cables are indicated for the transport and distribution of low voltage electricity. Their use is recommended for industrial connections, service connections, internal distribution and outdoor connections. They can be used in underground networks and permanent installations. The metal band provides greater protection against mechanical aggressions and the action of rodents.
Reference Standards
UNE 21123 and HD 603S1
Applications
- Underground networks for low voltage distribution
- Outdoor lighting installations
- Indoor or receiver installations
- Installations in premises with special characteristics






Technical Characteristics


1. Conductor |
Electrolytic copper, Class II, according to BS EN 60228:2005 (previously BS6360) and UNE 60228. |
---|---|
2. Insulation |
Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1 |
3. Armour bedding |
PVC |
4. Metallic armour |
Stainless steel |
5. Sheath |
PVC sheath |
Maximum temperature |
90 ºC |
Nominal voltage |
0,6/1 kV |
Test voltage |
3.500 V A.C. |
Other characteristics |
Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors) |
Dimensions
Section (mm2) |
Resistance at 20 °C (Ohm/km) |
External Diameter (mm) |
Weight (kg/km) |
Class |
---|---|---|---|---|
1x6 |
3,08 |
10,95 |
181 |
- |
1x10 |
1,83 |
12,45 |
233 |
Eca |
1x16 |
1,15 |
13,40 |
302 |
Eca |
Documents
Previous versions | ||
---|---|---|
Version | From | Until |
031-02 | 17/07/2017 | |
031-01 | 15/02/2017 | 17/07/2017 |