(+34) 976 500 120 | Contact us

Description


These cables comply with the construction product classification criteria according to the EU CPR Regulation 305/2011 and EN 50575, being those indicated for executing permanent installations where electromagnet protection is required to avoid parasitic currents. Their use is recommended in control applications of drivers, solenoid valves, start-up of machines and robots, remote switches, temperature, intensity and voltage regulation in motorised valves. Their flexibility makes them very appropriate in complex and extremely difficult installations.

Reference Standards

UNE 21123, HD 603 S1 and IEC 60502

Applications

Suitable for the following installations:
  • Underground networks for low voltage distribution
  • Underground supply networks for outdoor lighting installations
  • Electricity distribution networks
  • Underground service connectionsIndoor or receiver installations
  • Installations in premises with special characteristics

Industrial Outdoor lighting Maximum temperature 90 ºC Flexible Electromagnetic shielding RoHS CPR rated

Technical Characteristics

RVKV-K 0,6/1 kV RVKV-K 0,6/1 kV
1. Conductor

Flexible electrolytic copper, (Class V), according to BS EN 60228:2005 (previously BS6360) and UNE 60228.

2. Insulation

Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1

3. Concentric conductor bedding

PVC

4. Wire screen concentric conductor

Outer conductor of copper wires and contrahelical copper wires

5. Sheath

PVC Sheath type ST-1 according to UNE 21123 and IEC 60502-1

Maximum temperature

90 ºC

Nominal voltage

0,6/1 kV

Test voltage

3.500 V A.C.

Other characteristics

Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors)
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
The use of XLPE admits greater current density, at equal section, respect to the PVC insulation
CPR classification according to EN 50575

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)
Class

1x95/95

0,206

22,80

1.829

Eca

1x120/120

0,161

24,75

2.279

Eca

1x150/150

0,129

27,15

2.834

Eca

1x185/185

0,106

29,40

3.342

Eca

1x240/240

0,0801

31,05

4.301

Eca

1x300/300

0,0641

34,05

5.348

Eca

3x1,5/1,5

13,3

12,40

188

-

3x2,5/2,5

7,98

12,80

247

Eca

3x4/4

4,95

15,15

324

Eca

3x6/6

3,3

16,35

420

Eca

3x10/10

1,91

18,85

601

Eca

3x16/16

1,21

21,80

922

Eca

3x25/25

0,78

26,05

1.515

Eca

3x35/35

0,554

28,50

1.984

Eca

3x50/50

0,386

32,85

2.723

Eca

3x70/70

0,272

35,80

2.943

Eca

3x95/95

0,206

42,20

4.875

Eca

3x120/120

0,161

47,30

6.226

Eca

3x150/150

0,129

51,95

7.666

-

3x185/185

0,106

57,05

9.186

-

3x25/16

0,78

25,45

1.265

Eca

3x35/16

0,554

27,05

1.534

Eca

3x50/25

0,386

32,85

2.147

Eca

3x70/35

0,272

35,80

2.957

Eca

3x95/50

0,206

40,70

3.915

Eca

3x120/70

0,161

46,05

5.040

Eca

3x150/70

0,129

50,60

6.084

-

3x185/95

0,106

55,75

7.461

-

4x2,5/2,5

7,98

15,00

297

Eca

4x4/4

4,95

14,90

380

Eca

4x6/6

3,3

17,85

495

Eca

4x10/10

1,91

20,65

727

Eca

4x16/16

1,21

24,10

1.214

Eca

4x25/25

0,78

28,10

1.763

Eca

4x35/35

0,554

31,00

2.323

Eca

4x50/50

0,386

37,00

2.859

Eca

4x70/70

0,272

41,25

4.463

Eca

4x95/95

0,206

46,60

5.196

Eca

4x120/120

0,161

52,35

7.424

-

4x25/16

0,78

26,95

1.475

Eca

4x35/16

0,554

29,35

1.861

Eca

4x50/25

0,386

34,05

2.615

Eca

4x70/35

0,272

39,05

3.600

Eca

4x95/50

0,206

44,60

4.778

Eca

4x120/70

0,161

50,35

6.126

-

Newsletter

The data gathered through the next form will be used to send communications on our products and services. We use Elastic Email as our marketing automation service. By sending this form you agree with the transfer of the data to Elastic Email to be processed according to their terms of use and privacy policy.

Responsible: Cables RCT S.A.U. Purpose: To manage the submission of information and commercial prospecting. Legitimation: consent of the interested party. Recipients: Data will be transferred to Elastic Email for the automation of the submission. Rights: Access, correction and data erasure, as well as other rights, as explained in the additional information.Additional information on data protection is available on our website’s privacy policy