(+34) 976 500 120 | Contact us

RZ1KZ1-K (AS) 0,6/1 kV

Description


These cables are indicated for executing permanent installations where electromagnetic protection is required to avoid parasitic currents. Their use is recommended in control applications of drivers, solenoid valves, start-up of machines and robots, remote switches, temperature, intensity or voltage regulation in motorised valves as well as for installations in computer centres, airports, road tunnels, railways and anywhere where low fumes and corrosive gas emission is required in the event of fire, such as public premises, hospitals, schools and shopping centres.

Reference Standards

UNE 21123, HD 603 S1 and IEC 60502

Applications

Suitable for:
  • Underground supply networks for outdoor lighting installations

They can also be used in the following applications:
  • Underground networks for low voltage distribution
  • Electricity distribution networks
  • Underground service connections
  • Installations in premises with special characteristics
  • Appropriate for installations where greater fire protection is required.

Industrial Outdoor lighting Maximum temperature 90 ºC High Safety Flexible Electromagnetic shielding RoHS

Technical Characteristics

RZ1KZ1-K (AS) 0,6/1 kV RZ1KZ1-K (AS) 0,6/1 kV
1. Conductor

Flexible electrolytic copper, (Class V), according to BS EN 60228:2005 (previously BS6360)and UNE 60228.

2. Insulation

Cross-linked polyethylene (XLPE), type DIX-3, according to UNE 21123 and HD 603S1

3. Concentric conductor bedding

HFFR compound

4. Wire screen concentric conductor

Outer conductor of copper wires and contrahelical copper wires

5. Sheath

Thermoplastic polyolefin sheath type DMZ-E according to UNE 21123.

Nominal voltage

0,6/1 kV

Test voltage

3.500 V A.C.

Maximum temperature

90 ºC

Other characteristics

Colours according to UNE 21089 and HD 303S2 (colour marking when less than five conductors) and UNE-EN 50334 and EN 50334 (inscription marking when more than five conductors)
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
Non-fire propagating in accordance with UNE-EN 60332-3-24, EN 60332-3-24 and IEC 60332-3-24
Low halogen content according to IEC 60754-1 and 60754-2
Low corrosive gas emission according to IEC 60754-1 and 60754-2
Low opaque smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034
The use of cross-linked polyethylene (XLPE) admits greater current density, at equal section, respect to the insulation with PVC.

Dimensions

Section
(mm2)
Resistance
at 20 °C
(Ohm/km)
External
Diameter
(mm)
Weight
(kg/km)

1x95/95

0,206

21,30

1.775

1x120/120

0,161

23,50

2.245

1x150/150

0,129

25,75

2.779

1x185/185

0,106

27,95

3.343

1x240/240

0,0801

21,05

4.398

1x300/300

0,0641

34,20

5.497

3x1,5/1,5

13,3

12,30

190

3x2,5/2,5

7,98

13,05

236

3x4/4

4,95

14,55

314

3x6/6

3,3

15,65

400

3x10/10

1,91

17,95

583

3x16/16

1,21

20,20

828

3x25/25

0,78

23,85

1.222

3x35/35

0,554

27,35

1.682

3x50/50

0,386

31,80

2.349

3x70/70

0,272

36,40

2.937

3x95/95

0,206

41,70

4.247

3x120/120

0,161

46,65

5.389

3x150/150

0,129

51,25

6.668

3x185/185

0,106

56,40

8.169

3x25/16

0,78

23,85

1.150

3x35/16

0,554

27,35

1.527

3x50/25

0,386

31,80

2.142

3x70/35

0,272

36,40

2.937

3x95/50

0,206

41,30

3.877

3x120/70

0,161

46,65

4.977

3x150/70

0,129

51,25

6.008

3x185/95

0,106

56,40

7.353

4x2,5/2,5

7,98

13,95

273

4x4/4

4,95

15,60

367

4x6/6

3,3

16,95

474

4x10/10

1,91

19,35

692

4x16/16

1,21

21,70

979

4x25/25

0,78

26,00

1.468

4x35/35

0,554

28,75

1.953

4x50/50

0,386

36,45

2.958

4x70/70

0,272

41,05

3.974

4x95/95

0,206

45,25

5.075

4x120/120

0,161

51,45

6.535

4x150/150

0,129

56,25

8.039

Documents

Newsletter

The data gathered through the next form will be used to send communications on our products and services. We use Elastic Email as our marketing automation service. By sending this form you agree with the transfer of the data to Elastic Email to be processed according to their terms of use and privacy policy.

Responsible: Cables RCT S.A.U. Purpose: To manage the submission of information and commercial prospecting. Legitimation: consent of the interested party. Recipients: Data will be transferred to Elastic Email for the automation of the submission. Rights: Access, correction and data erasure, as well as other rights, as explained in the additional information.Additional information on data protection is available on our website’s privacy policy