Description
Cables Tri-Rated UL-CSA Style 1015 H07V2-U are used for internal wiring of control equipment (AWM, Appliance Wiring Material según UL 758) , in those places where special high temperature behaviour is required
Its standardisation, HD 21, BS 6231, UL 758 and CSA 22.2, makes it adequate to be marketed all over the world without technical barriers.
Reference Standards
BS 6231, UL 758, CSA 22.2, UNE-EN 50525-2-31, EN 5
Applications
Suitable for following installations:
- Internal or external wiring for electrical or electronic equipment.
- Installations in premises with special characteristics: premises at high temperature
Technical Characteristics
1. Conductor |
Electrolytic copper conductor, Class I, according to BS EN 60228:2005 (previously BS6360) and EN 60228.
|
2. Insulation |
PVC insulation, type TI-3, according to BS 6231, UL 758 and CSA 22.2, UNE 21031-7 and HD 21.7S2:1996/A1:1999.
|
Nominal voltage |
450/750 V UL 600 V BS 6231 0,6/1 kV
|
Test voltage |
2.500 V A.C.
|
Maximum temperature |
105 ºC
|
Other characteristics |
Colours according to UNE-EN 50525-1 and EN 50525-1
Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
PVC insulation with reduced hydrogen chloride (HCl) emission
CPR Classification according to EN 50575
|
Dimensions
Section (mm2) |
AWG |
Resistance at 20 °C (Ohm/km) |
External Diameter (mm) |
Weight (kg/km) |
Class |
1x1,5
|
16
|
12,1
|
2,80
|
20
|
Eca
|
1x2,5
|
14
|
7,41
|
3,30
|
30
|
Eca
|
1x4
|
12
|
4,61
|
3,80
|
45
|
Eca
|